Heat pump "air-water" / mini-cooler 30 AlcAW-air type
cooling rated operating conditions:
return air temperature - 35gradusov,
Incoming water - 12 gradusav,
The temperature of the outgoing water - 7 degrees
heating rated operating conditions:
return air temperature under a dry bulb thermometer - 7 degrees,
temperature wet bulb thermometer - 6 degrees,
The temperature of incoming water - 40 degrees,
water temperature - 45 degrees
Features:
functions
Nominal heating:
power heating. kW - 36,17
Btu / h - 123447
rated capacity, kW - 10.67
Rated current, A - 20.3 Nominal cooling
:
power cooling kW - 29,41
Btu / h - 100375
rated capacity, kW - 10.91
Rated current, A - 20.7
Maximum working current, A - 33.2
power, V / Ph / Hz - 380V / 3N / 50Hz
noise level, dB (A) - 65 Time
measures D m (A) x E (B) xB (C) - 1450h780h1253
Weight - 350
Management:
temperature accuracy - ± 1 degree
Operating Temperature - .. 20 ° ~ 45grad
Remote control:
Type - LCD display
General Features - operating mode, temperature, operating conditions, time
Throttling - Capillary
refrigerant:
Type - R417A.R410A
Compressor:
Type - Copeland, Sanyo, Daikin,
Qty - 2
protection function - Built-in safety device the protection cycle, undervoltage protection, protection against downtime
air heat exchange area:
Type - heat exchanger with finned heat exchange surface
Count, of pc - 2
fan type: < br /> Type - Axial fan with a large skew angle / angle of twist
motor power in kW - 0.6 water
heat exchange side:
Type - Effective flow heat exchangers
flow of water ( summer), m3 / h - 5,06
water flow (winter) m3 / h - 6,22
hydraulic pressure, k pa - 40
Dimensions compound inch - 1-1 / 2
working pressure water side, KPA - 1000