UPS Liebert NXC / NX possess three phases on the output and input. In the case of 10-20 kVA capacity can pick up device with a single phase. This monobloc system efficiency to 98%. Parallel connection of up to 4 power sources. The maximum capacity of the system - up to 240 kW. Power coefficient output - 1 (for models NX 30-60 kW). NXC series has a coefficient of 0.9. Double conversion, ECO-mode. Internal and external placement of the batteries. Intelligent charge control. Digital control current distribution. Remote control, the ability to provide remote control card. notifications Subscribe by email and over the network. in 12 languages interface. The duration of batteries under internal rooms: 5-65 min
Main characteristics and advantages of the UPS Liebert NXC / NX:
· efficiency of 96% (double conversion mode). 98% - ECO-mode;
· Output power factor 1 (kW = kVA for NX 30-40-60 KW series); 0.9 (for NXC series) - this allows you to feed the load more active power;
· Compact and UPS efficiency;
· Technology «True On-Line» double conversion; or ECO-mode;
· Batteries of various configurations - of the customer's choice, - placed inside of the cabinet (5 ... 65 minutes of battery life); or on the outside of the cabinet (for a multiple increase battery life)
· Intelligent management of battery charging, extending the time of their work;
· Digital technology current distribution management;
· Parallel connection of up to 4 UPS installation without centralized bypass cabinet;
· Wide range of input voltage and frequency for use in the most demanding conditions without using battery power;
· Compatibility with software LIFE®.Net - a unique system-clock remote monitoring, diagnostics . UPS status and warning of failures in real-time
· Compatible with Liebert Nform systems for remote monitoring and control of the UPS, MultiLink - to safely shut down the server equipment;
· monitoring via SNMP, WEB, ModBus with use existing local networks;
· Configuring monitoring signals and sending out notices of operating parameters on a local network, e-mail, etc. . Etc.
· Intuitive display representing the current information in 12 languages, including in Russian
· Convenient placements switching and installation;.
Besides the traditionally best-in performance class, highly reliable and flexible machines - new UPS Liebert NXC / NX record have high efficiency, the best performance and compactness in this case - is significantly lower cost than their predecessors legendary NXE / NXF. .
In terms of business - investment in uninterruptible power supply Liebert NXC / NX - the best investment in the monoblock UPS today
UPS Liebert NXC / NX is ideally suited for:
- any data center power < br /> - the server room
- industrial applications
- operate the medical facilities, banks, airports, hotels
- telecommunications facilities
- automation and process control centers
specifications:
Electrical characteristics (input rectifier):
- Rated power, KW - 60
- Nominal input AC voltage Vac. t -. 380/400/415 (three phases and neutral to total bypass input)
- The range of input voltages V AC. t -. 228-477
- frequency 50/60 Hz (range from 40 Hz to 70 Hz)
- Power Factor kW / KW, the total load (half load) - 0.99 (0, 98)
- power input kVA SG. (Max.) - 63,5 (72,5)
- input current A, nom. (Max.) - 92 (106)
- coefficient of harmonic current distortion, THDi,% FL - = 5 or less
- Duration soft start rectifier, s - 5 s . to reach the nominal current strength (supported change in the range of 1 to 5 seconds at 1 second intervals..)
Electrical characteristics (inverter output):
- Rated voltage AC , Vac. . T - 380/400/415 V (three-phase, five-wire connection to a neutral reference point connected to the neutral bypass)
- Frequency, Hz - 50/60
- Overload:
Long, % - 100-105
60 min,% - 105-110
10 min,% - 110-125
1 min,% - 125-150
Less than 200 ms,% > 150
- short circuit current,% - 310
- Nonlinear loads% - 100
- neutral current carrying capacity,% - 170
- Stability steady voltage,% ± 1
- voltage stability in dynamic mode, ± 5%
- total harmonic voltage distortion% <1 (linear load) <4 (non-linear load)
- synchronization window Hz ± 5 from the nominal frequency
- slew rate frequency (maximum variation of frequency synchronization),
Hz / s - 1; temperature range: from 0.1 to 3 (one module) or 0.2 (parallel system)
Environmental conditions:
- noise level at a distance of 1 m, dBA - 59
- The height above sea level, m - not more than 1000 meters above sea level; when working at height from 1000 m to 2000 m reduced power by 1% for every 100 m lift
- Relative humidity,% - From 0 to 95 (no condensation)
- Operating Temperature, ° C - From 0 to 40; a temperature increase per 10 ° C
than 20 ° C decreases the battery life twice
- UPS storage and transport temperature, ° C - -20 to +70
- Recommended temperature storage battery , ° C - -20 to 30 (20 ° C for optimal storage)
- overvoltage level - overvoltage level 2
- level of pollution - contamination level 2
Mechanical properties :
dimensions (W x D x), mm - 600 x 843 x 1600
weight without batteries kg - 260
weight with batteries kg - 630
Color - Black (ZP-7021)