Quantity
|
Out of stock
|
||
|
Specifications:
rated voltage - 12 V
power for 10 minutes. to 9.6V at 20 ° C - 1850 W Power
- / - 10 min do1.6V / cell at 20 ° C - 308 W
Capacity - 66 A / h
dimensions:
- length - 350 (± 0.7) mm
- width - 166 (± 0.5) mm
- height - 174 (± 0.5) mm
- weight - 23 kg
terminal Type:
with internal thread - M6
force - 4.8 Nm
Operating temperature range:
- storage (when fully charged) - -20 ° C to + 50 ° C
- at a charge of - -15 ° C to + 50 ° C
- during discharge - -20 ° C to + 50 ° C < br /> capacity loss per month at 20 ° C - 3%
body Material:
Standard delivery - ABS (UL.94: HB)
refractory body (modification FR) - ABS (UL.94: V0)
charging voltage:
charging voltage in standby at 20 ° C - 13.65 (± 1%)
temperature compensation voltage in standby (for deviations from 20 ° C) - -3 mV / cell / ° C
charging voltage cycled at 20 ° C - 14.5 (± 3%) in
temperature compensation voltage in a cyclic mode ( about tkloneniyah 20 ° C) - -4 mV / cell / ° C
charging current limiter (cyclic operation) - 16.5 A
Maximum charge current:
- 1 second - 800 A
- 1 minute - 500 A
internal resistance at 20 ° C - 9,35mOm
short circuit current - 1529 A
< br /> Lifetime according YUASA (at 20 ° C) - 10 years
Features:
- Yuasa battery can be used in any orientation, except for the use of a continuous inverted
- Standard. material - flame retardant to (UL94) HBSH
- material options FR - flame retardant to UL94:.. VIII (oxygen index 30)
- SWL batteries are manufactured in factories that meet the requirements of ISO9001: 2000 <. br /> - SWL batteries satisfy IEC 60896-21 + 22 specifications
Caution: Avoid
short-circuit Do not charge in a sealed container
service life... and operating characteristics depend on the operating temperature conditions ..
Interference on t AC reduces service life
performance and characteristics:.
- You can install and use in any position other than "upside down»
- Batteries must not be suspended by the handles ( if any)
- Each element is equipped with a vent valve for automatic pressure adjustment
- Batteries must be disposed of in accordance with applicable laws