Quantity
|
Out of stock
|
||
|
Specifications:
rated voltage - 12 V
power for 10 minutes. to 9.6V at 20 ° C - 1800 W Power
- / - 10 min do1.6V / cell at 20 ° C - 300 W
Capacity - 55 A / h
Dimensions: < br /> - length - 216 (± 0.7) mm
- width - 168 (± 0.5) mm
- height - 223 (± 0.7) mm
- weight - 23 kg
terminal Type:
with internal thread - M6 mm
force - 4.8 Nm
Operating temperature range:
- storage (at full charge) - -20 ° C to + 50 ° C
- at a charge of - -15 ° C to + 50 ° C
- during discharge - -20 ° C to + 50 ° C
capacity loss per month at 20 ° C - 3%
body Material:
Standard delivery - ABS (UL.94: HB)
refractory body (modification FR) - ABS ( UL.94: V0)
voltage charge:
charging voltage in standby at 20 ° C - 13.65 (± 1%)
temperature compensation voltage in buffer mode (deviations from 20 ° C) - -3 mV / cell / ° C < br /> charge voltage cycled at 20 ° C - 14.5 (± 3%) in
temperature compensation voltage in a cyclic mode (deviations from 20 ° C) - -4 mV / cell / ° C
charging current limiter (cyclic operation) - 13.75 A
Maximum charge current:
- 1 sec - 800 A
- 1 minute - 500 A < br />
internal resistance at 20 ° C - 10.09 mOhm
short circuit current - 1437 A
lifespan s according YUASA (at 20 ° C) - 10 years
Features:
- Yuasa Battery can be used in any orientation, except for the use of a continuous inverted
- Standard Material - flame retardant. . to (UL94) HBSH
- Material options FR - flame retardant to UL94: VIII (oxygen index 30)
- Battery SWL manufactured in factories that operate ISO9001 requirements:. 2000
-. SWL batteries satisfy IEC 60896-21 + 22 specifications
Warning:.
Do not short-circuit
Do not charge in a sealed container
The service life and op.. diet characteristics depend on the temperature operating conditions ..
Interference from AC reduces service life
performance and characteristics:.
- You can install and use in any position other than "upside down »
- Batteries must not be suspended by the handle (if present)
- Each element is equipped with a vent valve for automatic pressure adjustment
- Batteries must be disposed of in accordance with applicable laws