        Specifications: 
 nominal voltage -12 V 
 Capacity - 65 A / h 
 Dimensions: 
 - length - 350 (± 0,5) mm 
 - width - 166 (± 0,5) mm 
 - height - 174 (± 0,5) mm 
 - weight - 23 kg 
 terminal Type - terminal with internal thread M6 
 range Operating temperature: 
 - storage (when fully charged) - -20 ° C to + 60 ° C 
 - at a charge of - -15 ° C to + 50 ° C 
 - during discharge - -20 ° C to + 60 ° C 
 capacity loss per month at 20 ° C - 3% 
 body Material: 
 Standard delivery - ABS (UL.94: HB) 
 The refractory body (modification FR) - ABS (UL.94: V0) 
 charging voltage: 
 charging voltage in standby at 20 ° C - 13,65 (± 1%) 
 Temperature compensation voltage in buffer mode (deviations from 20 ° C) - -3 mV / cell / ° C 
 charging voltage cycled at 20 ° C - 14,5 (± 3%) in 
 Temperature compensation voltage in a cyclic mode (deviations from 20 ° C) - -4 mV / cell / ° C 
 charge current limit (CEC -crystal mode) - 16.25 
 A Maximum charge current: 
 - 1 sec - 800 A 
 - 1 minute - 500 A 
 Lifetime according YUASA (at 20 ° C) - 10 years 
 Performance and Features: 
 - You can install and use in any position other than "upside down" 
 - Batteries must not be suspended by the handles (if any) 
 - Each element is equipped with a vent valve for automatic pressure adjustment 
 - possible hydrogen evolution (for recharging). Do not install the battery in sealed cabinets 
 - Batteries must be disposed of according to current legislation 
    
 
                                    