Quantity
|
Out of stock
|
||
|
Application:
• For all purposes
• Uninterruptible Power Supply (UPS)
• The electricity system
• Emergency Standby Power
• Emergency lighting
• Railway alarm
• Samoletnaya alarm
• alarm and security systems
• Electronic devices and equipment
• DC power supply
• Automatic control system
specifications:
rated voltage - 12 V
Rated capacity (20 h) - 2.3 Ah
length - 178 mm Width
- 35 mm Height
ota - 60 mm Total height
conclusions - 66 mm
Weight - 1.00 kg
Terminal - T1
Rated power:
2.30 Ah / A 0.115 (20 hr., 1.80 V / cell, 25 ° C)
2,14 Ah / 0,214 A (10 hr., 1.80 V / cell, 25 ° C)
1,95 Ah / 0,39 A (5 hrs., 1.75 / elementt, 25 ° C)
1.79 Ah / 0.59 A (3 hr., 1.75 V / cell, 25 ° C .)
1.44 Ah / 1,44A (1 h, 1.60 V / cell, 25 ° C)
Maximum discharge current - 34.5 A
Internal resistance - 90 milliohms
Operating temperature range:
- Discharging: -15 - 50 ° C
- charge: 0 - 40 ° C
- Storage: -15 - 40 ° C
nominal operating temperature range - 25 ± 3 ° C
cyclic mode:
- charging current - is less than 0.69 A.
- eg 14.4 V- voltage 15.0 V at 25 ° C temperature coefficient of -30 mV / ° C
buffer mode:
- there are no restrictions on the charge current
- Voltage 13 5 V- 13,8 V at 25 ° C temp. coefficient of -20 mV / ° C
Effect of temperature on the vessel:
40 ° C - 103%
25 ° C - 100%
0 ° C - 86%
Self Discharge: Accumulators can be stored up to 6 months at a temperature of 25 ° C and then requires recharging. For higher temperatures the time interval will be shorter.