Charge-discharge Setting ZRUESA-80 (170) -100 intended for maintenance of alkaline batteries (AB) used for the energy supply trunk passenger railcars, technological handling equipment, telecommunications, etc. The apparatus provides automatic and manual modes of operation of the battery protection connection in wrong polarity exceeding the maximum allowable charge current (discharge). Polarity AB during the transition from the charge mode to the discharge mode and vice versa is performed manually. The control circuit thus switches to the appropriate mode automatically. In charge mode, a combined digital setting indicator displays the current process parameters (current, voltage across the battery and the time until end of charge). After the set time, tripping occurs automatically. In discharge mode, the digital device displays a combined discharge current, battery voltage and discharge time. Disabling the discharge current is performed manually by the operator. AB energy in the discharge mode back to the network. Features and characteristics of the device can be adapted to specific customer requirements. Specifications
- mains - three-phase, 50 Hz, 380 ± 10% of the earthed neutral;
- Power Consumption, kW, no more than - 22;
- maximum charge voltage stage 1, V - 80;
- maximum charging voltage stage 2, B-170;
- the control range of the battery (discharge) current of 10 A to 100;
- the value of tripping current overload, A - 105;
- long - mode;
- value instability charging (discharging) current,% - no more than 2;
- dimensions, mm - no more than 550h800h1600;
- weight, kg, not more than - 250;
- battery - capacitance elements 40 to 350A-hour (stage 1)
- battery. - up to 86 capacitance elements 350A-hour (2nd stage)
.