                                 Quantity 
                             | 
                            
                                 Out of stock 
                             | 
                        ||
| 
                                 | 
                        |||
        Number of wires - two 
 Material - Copper 
 Class - 1-thingwire 
 Insulation Material - PVC plasticized 
 insulation resistance (Mohm \ km) - 7 
 Cores ( Mom \ km) - 1.15 
 sheath Material - PVC plasticized 
 
 cable D (mm) - 16.5 
 cross section (mm2) - 16 
 Weight (kg \ km) - 456 
 copper Weight (kg / km) - 277.2 
 
 cable Application VVG 2x16: 
 With this power cable mark occurs and distribution of electric energy connection fixed installations at a voltage of 0.66 kV and a frequency of 50Hz. The gasket may be carried out in mines, cable racks, tunnels, and other technical facilities. The desired gasket in its environment in which the cable is exposed to low corrosivity, should not be tensile forces 
 
 Doing cable VVG 2x16:. 
 two cores, solid, made of copper wire. The cores are stranded, the cross section - 16 mm square. Insulation: insulation PVC-PLASTIC. From it is made and wire sheath. Coloring cable: usually black 
 
 Characteristics VVG cable 2 * 16: 
 Operation: When U SG equal to 0.66 kV, frequency 50 Hz 
 relative humidity, at work. wherein the cable is designed - 98% if the temperature is under 35 degrees 
 temperature range -. 50 ... + 50 degrees maximum T 
 heating copper wires is 70 degrees 
 At a temperature of 80 degrees heating cable this mark can work-NIL 8 hours (a day, during an emergency) 
 if a short circuit the maximum heating temperature of conductors - 160 degrees 
 time of its operation in compliance with the rules -. at least 25 years 
 R (electric) isolation of (1 km cable, 20 ° C) - no less than 7 ohms; 
 cable has an outer diameter of 16.5 square millimeters, a weight of 1 km cable is 456 kg. 
    
                                    