Protection device surge type 2
Scope
- types of networks (TN, IT, TT)
- connection method
- rated voltage
apparatus consisting of a varistor and a surge arrester encapsulated spark gap combined into module 1 + 1. To install a low-voltage switchgear in the border zones ZMZ 1 - 2. ZMZ serves to protect the wiring and equipment against surge caused by lightning and switching surges
Remote signaling optionally provided (S)
..
specifications: LN / N-PE
rated voltage Un - 230 V AC / -
maximum operating voltage Uc - 275 V AC / 255 V AC
nominal discharge current (8 / 20 s) / module In - 20 kA / 20 kA
Maximum discharge current (8/20) / Imax module - 40 kA / 40 kA
voltage protection level 5kA @ I = (8 / 20 microseconds) Up - 0.9 kV / -
protection level of the voltage Up - 1.35 kV / 1,5kV
response time ta - 25 ns / 100 ns
current breaking ability maintainer Ifl - no follow current / 100 A
protection against short-circuit protection at the maximum current 50 kArms / -
maximum current protection 160 gL / gG / -
protection class - IP 20 / IP 20
Engine s temperature range -40 ° C .. + 80 ° C
Fitting - DIN-rail 35
cross section connecting conductors:
- Single min / max ISO: 1/50 mm2; AWG: 17/1 ISO: 1/50 mm2; AWG: 17/1
- Stranded min / max ISO: 1/35 mm2; AWG: 17/2 ISO: 1/35 mm2; AWG: 17/2
The length of wire strippers - 14mm
Torque max - 4 N • m
Visual alarm fault - LED red / no
* Remote indication - Floating replaced contact / -
Contact remote signaling 250 V / 0,5 A AC, 250 V / 0,1 A DC / -
cross section conductors remote signaling max - 1,5 mm2 / -
compliance with the requirements of the standard EN 61643-11 + A11 T2 EN 61643-11 + A11 T2
Serial number SLP-275V / 1 + 1 8595090519485