Quantity
|
Out of stock
|
||
|
Heat pump "air-water" / mini-cooler 12 AlcAW-air type
cooling rated operating conditions:
return air temperature - 35gradusov,
Incoming water - 12 gradusav,
The temperature of the outgoing water - 7 degrees
heating rated operating conditions:
return air temperature under a dry bulb thermometer - 7 degrees,
temperature wet bulb thermometer - 6 degrees,
The temperature of incoming water - 40 degrees,
water temperature - 45 degrees
Features:
functions
Nominal heating:
power heating. kW - 14,87
Btu / h - 50751
rated capacity, kW - 4.48
Rated current, A - 8.5
Nominal cooling:
power cooling kW - 12,09
Btu / h - 41263
rated capacity, kW - 4.58
Rated current, A - 8.7
Maximum working current, A - 13.9
power, V / Ph / Hz - 380V / 3N / 50Hz
noise level, dB (A) - 55
size, m D (A) x E (B) xB (C) - 810h780h1050
Weight - 155
Management:
temperature accuracy - ± 1 degree
Operating temperature -20 deg. . ~ 45grad
Remote control:
Type - LCD display
General Features - operating mode, temperature, operating conditions, time
Throttling - Capillary Refrigerant
< br /> Type - R417A.R410A
Compressor:
Type - Copeland, Sanyo, Daikin,
Qty - 1
protection function - Built-in overheat protection device cycle protection , undervoltage protection, protection from idle
air heat exchange zone:
Type - heat exchanger with finned heat transfer surface
Max, pc - 1
fan Type:
Type - Axial fan with a large skew angle / angle of twist
motor power in kW - 0.3 water
heat exchange side:
Type - Effective flow heat exchangers
Feed water (summer) m3 / h - 2,08
Feed water (winter) m3 / h - 2,56
Hydraulic pressure, kpa - 30
Dimensions compound inch - 1
working pressure water side, KPA - 1000