Quantity
|
Out of stock
|
||
|
1 Purpose
1.1 Voltage converter 24V DC IPI.24V / 220V.1,0kVA.50Hz current (hereinafter - the converter) designed receivers for feeding power to the power consumption to 1000VA single phase 220V 50Hz AC
1.2 converter is designed for continuous clock work indoors under the following environmental conditions:
- ambient temperature from 0C to + 40C;.
- relative humidity to 95% at a temperature of + 25C
2 basic specifications and characteristics
2.1 Standard value DC supply voltage 24V
2.3 valid range of DC supply voltage (21 ... 32) In.
2.4 Standard value AC output voltage (220 4) .
2.5 The nominal value of the frequency vyhodnog of voltage (50 1) Hz
2.6 Nominal load value total power 1000VA
2.7 Work load power range from 0 to 100% of nominal load
2.8 Type -... active, active- . inductive, capacitive-active, non-linear (rectifier filter)
2.9 Operating range of load power factor 0.7 ... 1
2.10 overload power factor of 1.7:. 1 during 5c
2.11 ratio distortion sinusoidal output voltage at rated power active load, not exceeding 10%.
2.12 The current consumed by the converter at nominal input voltage and full load power, not more than 50A.
2.13 converter has protection overload and short-circuit of the load from a reduced voltage or increased power, incorrect polarity of a voltage supply and overheating.
2.14 Automatic disconnection occurs at a converter output voltage electron ropitaniya of range. Automatic activation of the transducer occurs when returning power within the operating range.
2.15 Dielectric strength between the closed and the input terminals of the converter housing between the closed and the output terminals of the converter housing, and between the closed and the input terminals of the inverter outlet closed, can withstand without breakdown test voltage of 1000 V alternating current frequency of 50 Hz (effective value) in the for 1min.
2.16 Efficiency converter at nominal input voltage and full power of the load, at least
0.85 2.17 Cooling method -. forced ventilation with temperature control of the air supply
2.18 Dimensions converter (Wxhxd, without protrusions) 255x85x190mm. .
2.19 converter Weight, no more than 4.5 kg.