Quantity
|
Out of stock
|
||
|
Inverter IPI 220V / 220V 5kVA 50Hz
1 Purpose
1.1 voltage 220V DC-DC converter IPI.220V / 220V 5kVA.50Hz (hereinafter - the converter) designed to supply different power receivers with a power consumption of up to . 5000VA single phase 220V 50Hz AC
1.2 converter is designed for continuous clock work indoors under the following environmental conditions:
- environment temperature from 0C to + 40C;
- relative humidity to 95% at a temperature of + 25C.
2 basic specifications and characteristics
2.1 nominal value of 220V dc supply voltage.
2.2 Operating voltage range power supply DC current (180 ... 264) In.
2.3 Permitted voltage DC power range (170 ... 270) In.
2.4 Standard value AC output voltage (220 + -3) in.
2.5 The nominal value of the frequency . S output voltage (50 + -1)
2.6 Hz maximum value of the total load power 5000VA
2.7 Operating range of load power of from 0 to 100% of nominal load
2.8 Type -.. Active ., an active-inductive, capacitive, active-nonlinear (rectifier filter)
2.9 Operating range of load power factor 0.7 ... 1
2.10 overload power factor of 1.5:. 1 for 5c.
2.11 distortion coefficient sinusoidal output voltage at rated power active load, not exceeding 10%.
2.12 The current consumed by the converter at nominal input voltage and full load power, not more than 26A.
2.13 The converter has an overload protection and short circuit across the load reduced from a high input voltage of reverse polarity power supply voltage, and from overheating.
2.14 Automatic disconnection occurs at a converter output voltage Power of range. Automatic activation of the transducer occurs when returning to power supply voltage operating range.
2.15 Dielectric strength between the closed and the input terminals of the converter housing between the closed and the output terminals of the converter housing, and between the closed and the input terminals of the inverter outlet closed, can withstand without breakdown 1000V test voltage (effective value).
2.16 Efficiency converter at nominal input voltage and full load power at least
0.88 2.17 Cooling method -. forced ventilation with temperature control of the air supply
2.18 Dimensions converter (Wxhxd, without protrusions) 410x90x325mm. .
2.19 converter Weight, no more than 12,0kg.