UPS-20000L3
Three-phase UPS with double conversion (On-Line)
* On-Line
*
* Three-phase power 20000VA / 14000Vt
* pure sine wave
* connectable external battery 240V (optional)
* 10 ampere battery charging
* microprocessor control
* function of voltage stabilization cold
* start
* protection against short-circuit, overload and over-discharge battery,
* USB interface
specifications
Power LOG 14000Vt
Operating voltage 304-478V / three-phase
frequency 46-54 Hz
OUTPUT voltage type (battery operation) correct
sinusoid output voltage (during operation network) 220V +/- 2%
output voltage (battery operation) 220V +/- 2%
frequency (battery operation) 50 +/- 0,2% Hz
Automatic adjustment of voltage (integrated voltage stabilizer) device may pa bot without batteries connected as a voltage stabilizer
Switching Time 0ms technology double conversion UPS functions
double conversion UPS technology voltage output voltage in a regular sine wave, and a power saving function
Cold start ( without connecting to an external network device) has
protection and filtration
Surge suppression (Surge) complete suppression of interference from the external network
protection input fuse into the input jack, electronic protection
overload protection Automatic shutdown during overload:
120% for a minute
150% for three seconds
protection against short-circuit or disabling automatic operation of the fuse
BATTERY
Type lead-acid, sealed,
capacity and the number / specified for an external battery voltage 240V external
Automatic charging of batteries (for models with external battery), the battery current, a ma GUT automatically reguliret current Zardi vnesheny battery
Protection Protection against overcharging and undercharging, the self-discharge compensation
mass and dimensions
Weight device kg 55kg
Weight kg. 72kg
Dimensions apparatus mm D x W x H, mm 260 x 570 x 720
SOCKETS Input socket
Output sockets
SIGNALS
Battery operation Repeating signal once 4 seconds, with disconnection
Repeatable Battery Low 1 signal per second
continuous overload signal
aMBIENT CONDITIONS Operating environment Altitude up to 3,500 meters, moisture
0-95% non-condensing, 0-40`S
Acoustic noise <40dBA at 1 meter
Storage Altitude up to 15,000 meters