Cordless balancer equalizes state of charge of two series-connected 12V lead-acid accumulators or more parallel rows of serially connected batteries. When the system 24 to charge battery voltage exceeds 27.3 The balancer compares the voltage on and two series-connected batteries. Rocker provide balancing current to 0, 7 A battery (or batteries connected in parallel) with the highest voltage. As a result, the batteries will have the same state of charge. For the battery 48 uses three rocker
LEDs and the alarm relays:.
Green: on when the battery voltage is more than 27.3 V.
Orange: is included at a deviation of more than 0.1 In the "bottom" side of the battery
Orange:. engaged when a deviation of 0.1 in the "upper" side of the battery
Red:. alarm (deviation of more than 0, 2).
alarm relay: normally open contact closes when the red LED is turned on. Contact remains closed to reduce the deviation to 0.14 V or to reduce the battery voltage to 26.6 V. Reset signal relay is performed using the button to be connected to two terminals
Specifications:.
input voltage range of the battery, V - Up to 18 in battery 36 -
total inclusion level, V - 27,3 ± 1%
off level, V - 26,6 ± 1%
current consumption during off rocker mA - 0.7
deviation midpoint to start balancing mV - 50
maximum current balancing, A - 0.7 (with a deviation of 100 mV)
level deviation to activate an alarm, mV - 210
deviation level to reset the alarm, mV - 140
alarm relay - 60 V / 1 A (normally open)
turn off the alarm relay - Two terminals for connecting the < br /> protection against overheating - there
Operating temperature - from -30 to +50 degrees C
Humidity (non-condensing) - 95%
The body:
color - Blue (RAL 5012)
terminals - Win nels terminals 6 mm? / AWG10
Protection - IP22
Weight 0.4
Dimensions (VxShx.G), mm - 100h113h47